Prev Next Protective Relay Voltage Relay EP4-2 MULTI FUNCTION VOLTAGE RELAY Add to inquiry Inquiry list Description Wiring and timing diagrams Overall dimensions or other Download Switching Mode Power Supply architecture 3-phase 3-wire and 3-phase 4-wire selectable via DIP switch multi-voltage selectable via DIP switch (please see table below) Over Voltage trip point from 5 to 20% Under Voltage trip point from 5 to 30% Voltage Trip Delay from 0.1 to 30 sec. Voltages Unbalance detection with a fixed 3 sec. trip delay Voltages Unbalance trip point from 2~22% or turned off Phase Lost detaton with 0.2 sec. trip delay Phase Reversal detection prior to load engagement or turned off via DIP switch Auto reset time selectable between 1 and 5 sec. EP4-2 Catalogue EP4-2 User Manual