Next Protective Relay Voltage Relay EP2-2 3-PHASE POWER MONITORING RELAY Add to inquiry Inquiry list Description Wiring and timing diagrams Overall dimensions or other Download Switching mode power supply design User selectable operating/monitoring voltage range:3P3W:208, 220, 240, 380, 400, 415, 480V 3-phase voltage fault monitoring:Phase reversal, Phase loss, Over voltage, Under voltage Over voltage:2~22% Under voltage:2~22% Over/under voltage trip delay time:0.1~30 sec Phase loss delay time:0.2 sec fixed Reset delay time:1sec EP2-2 Catalogue